Cellular glass — closed-cell, non-absorbent insulation. Default choice for cryogenic & cold service down to –269 °C.
Applicable Standards (5)
ASTM — 2 standards
ASTM C552
Cellular Glass Thermal Insulation
Cellular glass (Foamglas-type) insulation — preferred for cold/cryogenic service down to about −260 °C; non-combustible, closed-cell, water-impermeable.
Key requirements (8)
- Cellular glass thermal insulation — Foamglas™ class material.
- Closed-cell, 100% inorganic glass foam — non-absorbent (zero water uptake).
- Service temperature: –269 °C to +482 °C (cryogenic to hot service).
- Thermal conductivity: ~0.040 W/m·K at 24 °C; ~0.033 at –40 °C.
- Compressive strength: 414 kPa (Type II), 690 kPa (Type IV) — load-bearing capable.
- Density: ~120 kg/m³.
- Default cryogenic insulation under cellular glass-cellular glass joints; resists liquid water ingress.
- Non-combustible per ASTM E136.
Note: Default cold-service insulation for cryogenic LNG / ethylene / ammonia and cold-box applications.
ASTM C585
Inner and Outer Diameters of Thermal Insulation for Nominal Sizes of Pipe and Tubing
Standardized pipe-insulation sizing tables.
CINI — 1 standard
CINI Manual
Insulation for Industries (CINI Manual)
Dutch industrial insulation manual — hot, cold, cryogenic, fire-protection, personnel-protection. Widely adopted across Europe and global EPC projects.
Key requirements (6)
- Dutch / European specification for industrial insulation manual.
- Sheet 2.1.01 onward: design data for hot insulation.
- Sheet 3.1.01 onward: cold insulation including cryogenic.
- Vapor barrier integrity test methods for cold service.
- Materials: cellular glass, PIR, mineral wool, aerogel guidance.
- Joint sealing details for cold insulation continuity.
BSI — 1 standard
BS 5970
Code of practice for thermal insulation of pipework, ductwork, vessels and equipment in the temperature range −100 °C to +870 °C
Application code for hot and cold thermal insulation in industrial service.
Key requirements (6)
- Code of practice for thermal insulation of pipework, ducts, vessels.
- Covers hot insulation, cold insulation, personnel protection, frost protection.
- Thickness selection charts based on heat loss / surface temperature targets.
- Vapor barrier requirements for cold service detailed.
- Cladding / metal jacketing specifications.
- Personnel protection target: surface temperature ≤ 60 °C.
BIS — 1 standard
IS 14164
Industrial Insulation Work — Code of Practice
Indian application code for industrial insulation (hot and cold).