Category
Electrical Systems
Subcategory
Protection
Applicable standards
3
Issuing bodies
3
Description
External & internal lightning protection per IEC 62305 / NFPA 780.
Applicable Standards (3)
IEC — 1 standard
IEC 62305 (series)
Protection against lightning
Lightning protection system design — risk assessment, air termination, down conductors, earth termination, internal LPS.
Key requirements (7)
- Lightning protection: Parts 1 (general), 2 (risk), 3 (physical), 4 (electrical/electronic).
- Lightning protection level (LPL): I (highest, 99% capture), II (97%), III (91%), IV (84%).
- Air termination: rolling sphere method (radius 20/30/45/60 m for LPL I/II/III/IV).
- Mesh method: 5/10/15/20 m mesh size for LPL I/II/III/IV.
- Down conductors: spacing ≤ 10/10/15/20 m around perimeter.
- Earth termination: type A (radial / vertical) or type B (ring) — < 10 Ω target typical.
- Surge protection: SPD coordination (Type 1 / 2 / 3) at incomer, sub-distribution, equipment.
NFPA — 1 standard
NFPA 780
Standard for the Installation of Lightning Protection Systems
Lightning protection system design (US counterpart to IEC 62305).
BIS — 1 standard
IS/IEC 62305 (series)
Protection Against Lightning
Indian adoption of IEC 62305 lightning protection.