← All standards & equipment
Instrumentation & Control

Temperature Sensor — RTD

Platinum resistance temperature sensor (Pt100 / Pt1000) per IEC 60751.

Category
Instrumentation & Control
Subcategory
Temperature
Applicable standards
2
Issuing bodies
2

Description

Platinum resistance temperature sensor (Pt100 / Pt1000) per IEC 60751.

Applicable Standards (2)

ASME — 1 standard

ASME PTC 19.3 TW Thermowells — Performance Test Codes
Edition: 2016 Edition Region: USA, Global
Strength and stability calculation of thermowells (vortex shedding, frequency, stress).
Key requirements (8)
  • Thermowells — design and stress analysis (also as ASME PTC 19.3 TW).
  • Velocity-induced vibration: avoid resonance (natural frequency ≥ 80% of vortex shedding frequency × scale factor).
  • Strouhal number: 0.22 typical for cylinder in cross flow.
  • Stress check: bending + drag + axial — combined < material allowable.
  • Wake frequency formula (Strouhal): fw = St·V/D where D = thermowell tip diameter.
  • Frequency ratio limit: scaling factor 0.4 (lock-in zone) to 0.8 (resonance).
  • Mounting: threaded, flanged, socket-weld, welded.
  • Insertion length (U): immersion depth into pipe; balance of response time vs vibration.

IEC — 1 standard

IEC 60751 Industrial platinum resistance thermometers and platinum temperature sensors
Edition: 2022 Region: Global
Pt100 / Pt1000 RTD reference tables, tolerance classes (AA, A, B, C).