Issuing body
NFPA
Latest edition
2025
Region
USA, Global
Equipment items
1
Scope
Fire water pump installation, controllers, drivers, testing.
Key requirements (8)
- Stationary fire-protection pumps — electric, diesel, steam-driven.
- Pump types: horizontal split-case, end-suction, vertical-inline, vertical-turbine, multistage.
- Performance: minimum 100% rated flow at 65% rated head and 150% rated flow at 65% head (rough rule).
- Listed/labeled pumps (UL, FM) required.
- Diesel driver: dedicated fuel for ≥ 8 hours; 2 batteries; weekly run test.
- Jockey pump (pressure maintenance): not for fire flow — sized to maintain system pressure.
- Suction conditions: positive head preferred; flooded suction with ≥ 150% rated capacity available.
- Annual full-flow testing required.
Related standards (1)
Applied to 1 equipment item
Rotating Equipment