HomeInstrumentation Calculators › Instrument Loop Calculator
Instrumentation · Loop Integrity

Instrument Loop Calculator

Check cable voltage drop and transmitter headroom on a 4-20 mA current loop — worst case at 20 mA and at the 22 mA HART diagnostic peak.

4-20 mA · IEC 60381-1
🔌Loop Integrity Calculator
Enter values and press Calculate to see the loop analysis.
Worked example

A transmitter sits 500 m from the marshalling cabinet on 1.5 mm² twisted-pair cable at 20°C. Supply is 24 V, the transmitter needs at least 12 V, and the receiving instrument burden is 250 Ω.

Cable R = 11.2 Ω → Total loop Z = 261.2 Ω → V at Tx (20 mA) = 18.776 V → Headroom = 6.776 V — PASS

The form above is pre-filled with these exact numbers — press Calculate to reproduce this result, or change the inputs for your own loop.

Formula & variable legend
Rcable = ρCu(T) × 2L / A
ρCu(T) = 0.0168 × (1 + 0.00393 × (T − 20))
VTx = Vsupply − (Rcable + Rburden) × I
Headroom = VTx − VTx,min
L — one-way cable length, m (doubled in the formula for the return conductor)
A — conductor cross-sectional area, mm²
T — cable temperature, °C (20°C reference)
I — loop current: 0.020 A worst-case, 0.022 A at HART diagnostic peak
Rburden — receiving instrument / loop burden resistance, Ω
📋Accepted inputs
FieldAccepted rangeNotes
Cable length> 0m, km or ft
Cable cross-section> 0mm² or AWG (10–28 tabulated, other gauges computed)
Supply voltage> 0V
Transmitter min voltage> 0, < supplyV
Loop burden≥ 0Ω
Cable temperature−50 to 200°CDefaults to 20°C if left blank
Headroom status examples
Cable / CSAHeadroom @ 20 mAStatus
500 m / 1.5 mm²6.78 VPASS at 20 mA and 22 mA
5000 m / 0.5 mm²0.28 VPASSES 20 mA, FAILS 22 mA diagnostic
6000 m / 0.5 mm²−1.06 VFAILS at 20 mA

Frequently asked questions

What is an instrument loop voltage drop calculation?
A 4-20 mA loop is a series circuit: the power supply, the cable resistance, and the transmitter's own burden all share the same current and each drop some voltage. This calculator adds up the cable and burden voltage drops at worst-case 20 mA and checks whether enough voltage is still left over (headroom) for the transmitter to operate correctly.
Why does cable temperature affect the loop calculation?
Copper's resistivity rises with temperature (about 0.393% per °C above 20°C). A cable run through a hot area or outdoors in summer has measurably higher resistance than its rated value at 20°C, which increases the voltage drop and reduces headroom at the transmitter. Enter the expected cable temperature to get a realistic worst-case number rather than a 20°C best case.
What headroom should I target at the transmitter?
Most transmitter manufacturers specify a minimum operating voltage; anything above that is headroom. Industry practice is to keep at least 2 V of headroom at 20 mA and to size the supply at 1.3 × the transmitter's minimum voltage plus loop drop for a comfortable safety margin — tight headroom leaves no room for supply sag, connector resistance, or added devices later.
Why check the loop at 22 mA as well as 20 mA?
Smart (HART) transmitters can briefly output up to 22-24 mA during diagnostics or alarm conditions, above the nominal 20 mA full-scale signal. A loop that just barely passes at 20 mA can collapse when the transmitter tries to signal a diagnostic fault at 22 mA — this calculator checks both currents so a diagnostic event doesn't take the loop down.
What's the difference between this calculator and the Loop Power Supply Calculator?
This calculator works from physical cable properties — length, cross-sectional area, and temperature — to derive cable resistance and voltage drop. The Loop Power Supply Calculator instead works from a component budget — barrier, isolator, and other fixed resistances you already know — to check the same headroom question without needing cable geometry.
Instrument Loop Calculator  |  Instrumentation Calculators  |  multicalci.com