Category
Insulation & Refractory
Subcategory
Cold / Cryogenic Insulation
Applicable standards
5
Issuing bodies
4
Description
Rigid PIR / PUR foam insulation for refrigerated & cold service (down to ~ –180 °C).
Applicable Standards (5)
ASTM — 2 standards
ASTM C591
Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
Rigid PIR/PUR insulation for pipes and equipment, typically −180 °C to +120 °C.
Key requirements (7)
- Polyisocyanurate (PIR) rigid cellular foam insulation.
- Service temperature: –183 °C to +149 °C.
- Thermal conductivity: ~0.022 W/m·K at 24 °C (initial); ~0.026 aged.
- Closed-cell, low water absorption.
- Density: 32–50 kg/m³ typical; 40–96 kg/m³ for higher compressive grades.
- Used widely for refrigerated piping, LPG/ammonia storage tank base insulation.
- Combustible — needs fire protection in high-risk areas.
ASTM C585
Inner and Outer Diameters of Thermal Insulation for Nominal Sizes of Pipe and Tubing
Standardized pipe-insulation sizing tables.
CINI — 1 standard
CINI Manual
Insulation for Industries (CINI Manual)
Dutch industrial insulation manual — hot, cold, cryogenic, fire-protection, personnel-protection. Widely adopted across Europe and global EPC projects.
Key requirements (6)
- Dutch / European specification for industrial insulation manual.
- Sheet 2.1.01 onward: design data for hot insulation.
- Sheet 3.1.01 onward: cold insulation including cryogenic.
- Vapor barrier integrity test methods for cold service.
- Materials: cellular glass, PIR, mineral wool, aerogel guidance.
- Joint sealing details for cold insulation continuity.
BSI — 1 standard
BS 5970
Code of practice for thermal insulation of pipework, ductwork, vessels and equipment in the temperature range −100 °C to +870 °C
Application code for hot and cold thermal insulation in industrial service.
Key requirements (6)
- Code of practice for thermal insulation of pipework, ducts, vessels.
- Covers hot insulation, cold insulation, personnel protection, frost protection.
- Thickness selection charts based on heat loss / surface temperature targets.
- Vapor barrier requirements for cold service detailed.
- Cladding / metal jacketing specifications.
- Personnel protection target: surface temperature ≤ 60 °C.
BIS — 1 standard
IS 14164
Industrial Insulation Work — Code of Practice
Indian application code for industrial insulation (hot and cold).