MULTICALCI
Home / Electrical Calculators / Cable Size Calculator
Electrical Engineering

Cable Size Calculator

Find the minimum conductor cross-sectional area that keeps voltage drop inside your chosen limit, and get the combined IEC 60364-5-52 derating factor for ambient temperature, circuit grouping and installation method. Resistance is evaluated at your stated operating temperature and the reactive component is included in the sizing.

IEC 60364-5-52 IEC 60228 IEC 60287 BS 7671
🔌 Load & Route
The size you intend to use. The calculator checks it and also reports the minimum that would pass.
5 % general, 3 % lighting per IEC 60364-5-52 Annex G.
Used for the resistivity correction, not for derating.

Enter your values and select Calculate.
Scope: this tool sizes the conductor on voltage drop and reports the derating product k. It does not compare your design current against a tabulated ampacity — that check needs the ampacity table for your specific cable construction and installation method. Take the reported k, multiply it by the table value, and confirm the result exceeds Ib. Size the cable on whichever answer is larger.

Cable Sizing Formulae

Amin = k · Ib · L · ρT · cos φ / ( ΔUmax − k · Ib · x′ · L · sin φ )
ΔU = k · Ib · ( R · cos φ + X · sin φ ) // drop at the trial size
R = ρT · L / A  ·  X = x′ · L
ρT = ρ20 · [ 1 + α · (T − 20) ]
ktotal = kT × kG × kI // apply to tabulated ampacity
Iz = It × ktotal ≥ Ib // the ampacity check, done separately
SymbolMeaningUnit
AminMinimum conductor area for the voltage drop limitmm²
IbDesign current of the circuitA
ItTabulated ampacity for the installation methodA
IzDerated current-carrying capacityA
kPhase multiplier — √3 three phase, 2 single phase
ρTResistivity at operating temperatureΩ·mm²/m
αTemperature coefficient — 0.00393 Cu, 0.00403 Al1/K
x′Reactance per metre from the formation tableΩ/m
ΔUmaxPermitted drop in voltsV
kT, kG, kITemperature, grouping and installation factors

Worked Example

200 A three-phase submain, 415 V, 120 m, 95 mm² copper at 40 °C

A 200 A distribution board is fed by a 120 m run of 95 mm² copper, laid in trefoil on open tray at a 40 °C conductor temperature, power factor 0.85, with a 5 % voltage drop allowance.

Resistivity at 40 °C
ρT = 1.72e-8 × [1 + 0.00393 × 20] = 0.01855192 Ω·mm²/m
Conductor resistance
R = 0.01855192 × 120 / 95 = 0.023434 Ω
Conductor reactance
X = 0.08e-3 × 120 = 0.0096 Ω
Voltage drop at 95 mm²
ΔU = √3 × 200 × (0.023434 × 0.85 + 0.0096 × 0.5268) = 8.652 V
Percentage drop
8.652 / 415 × 100 = 2.08 % — inside the 5 % limit
Minimum CSA for 5 %
34.50 mm² → next standard size 35 mm²
Power loss
P = 3 × 200² × 0.023434 = 2812.1 W
Resistance per km
0.01855192 × 1000 / 95 = 0.1953 Ω/km
Current density
200 / 95 = 2.1053 A/mm²
Derating product
k = 0.87 × 1.00 × 1.00 = 0.87
ΔU = 8.652 V (2.08 %) · Amin 34.50 mm² · loss 2812.1 W · k 0.87
Voltage drop allows 35 mm², but 200 A of design current will not fit in 35 mm² on ampacity — a 95 mm² copper cable on tray is around 250 A tabulated, giving Iz = 250 × 0.87 = 217 A against Ib = 200 A. This is why the ampacity leg decides most short runs and voltage drop decides most long ones.

Units & Accepted Ranges

InputUnitAccepted rangeDefault
Phase systemSingle or three phaseThree phase
System voltageV> 0415
Design current IbA> 0200
Power factor> 0 and ≤ 10.85
Route lengthm (ft)> 0120
Trial CSAmm² (kcmil)> 095
Permitted drop%> 05
Operating temperature°C−30 to 90, not exactly 040
kT, kG, kI> 0 and ≤ 10.87, 1.00, 1.00
Above 90 °C the linear resistivity correction under-reads and IEC 60287 methods are required. Above 150 mm² skin and proximity effects raise the effective AC resistance. The calculator flags both conditions.

IEC 60364-5-52 Derating Factors

Ambient temperaturekT — 70 °C PVCkT — 90 °C XLPE
25 °C1.061.04
30 °C (reference)1.001.00
35 °C0.940.96
40 °C0.870.91
45 °C0.790.87
50 °C0.710.82
55 °C0.610.76
Circuits in the groupkG — bunched, touchingkG — single layer on tray
11.001.00
20.800.88
30.700.82
40.650.79
60.570.76
90.500.73
120.450.72
Values are representative of the IEC 60364-5-52 Annex B tables for preliminary sizing. Use the exact table row for your installation method and cable construction on project work.

Standard Conductor Sizes (IEC 60228)

CSA (mm²)Approx. kcmilCu R at 20 °C (Ω/km)Al R at 20 °C (Ω/km)
2.54.96.88011.280
47.94.3007.050
611.82.8674.700
1019.71.7202.820
1631.61.0751.763
2549.30.6881.128
3569.10.4910.806
5098.70.3440.564
70138.10.2460.403
95187.50.1810.297
120236.80.1430.235
150296.00.1150.188
185365.10.0930.152
240473.60.0720.118
300592.10.0570.094
400789.40.0430.071
Resistances are the ideal ρ/A value at 20 °C. Real stranded cables run a few percent higher because of the lay factor; take Ω/km from the manufacturer catalogue for tender work.

Frequently Asked Questions

How do I calculate the correct cable size?

Cable sizing is a three-part check and the largest answer wins. First, current-carrying capacity: the tabulated ampacity for the installation method, multiplied by the derating factors, must be at least the design current. Second, voltage drop: the conductor must be large enough to keep the drop within the permitted percentage over the route length. Third, short-circuit withstand: the adiabatic check k·S must exceed the fault energy over the protection clearing time. This calculator solves the voltage drop leg and reports the combined derating factor for the ampacity leg.

What are cable derating factors and when do I apply them?

Derating factors reduce a cable's tabulated current-carrying capacity to account for conditions worse than the reference case. IEC 60364-5-52 gives three principal factors: ambient temperature correction, typically 0.87 at 40 °C for a 90 °C XLPE cable; grouping correction, which falls as more circuits share a route, around 0.80 for four circuits touching; and an installation method or thermal insulation factor. Multiply all three together and apply the product to the table value before comparing against your design current.

Does this cable size calculator check current-carrying capacity?

No. It sizes the conductor on voltage drop and reports the combined derating factor, but it does not compare your design current against a tabulated ampacity, because that requires the ampacity table for your specific cable construction and installation method. Take the derating product reported here, multiply it by the tabulated ampacity from IEC 60364-5-52 Annex B or your manufacturer catalogue, and confirm the result exceeds the design current. Use whichever is larger — that answer or the minimum CSA reported here.

Should I use copper or aluminium cable?

Aluminium has about 65 % higher resistivity than copper, so for the same voltage drop an aluminium conductor needs roughly 1.6 times the cross-sectional area, usually one or two standard sizes larger. Against that, aluminium is substantially cheaper per metre and about a third of the weight, which matters on long runs and large sizes. Aluminium terminations need bimetallic lugs and correct torque because the oxide layer and higher creep make joints the usual failure point.

What is the maximum cable size before skin effect matters?

Above roughly 150 to 185 mm² the skin and proximity effects begin to raise the effective AC resistance measurably above the DC value, so a calculation based on DC resistivity starts to under-read losses and voltage drop. IEC 60287 defines the ys and yp factors that quantify this. In practice, engineers avoid the problem by running multiple smaller cables in parallel rather than one very large conductor, which also improves handling and termination.

Related Electrical Calculators

← All Electrical Engineering Calculators

Results are for estimation and preliminary design. Cable selection must satisfy current-carrying capacity, voltage drop and short-circuit withstand together. Verify against project specifications, cable manufacturer data and a qualified engineer before construction.

multicalci.com — free engineering calculators