MULTICALCI
Home / Electrical Calculators / Voltage Drop Calculator
Electrical Engineering

Voltage Drop Calculator

Calculate the voltage drop along a cable run for single-phase or three-phase circuits. Conductor resistance is evaluated at 75 °C and the calculation includes the cable reactance term, so the result stays valid at low power factor and on larger conductors where a resistance-only estimate under-reads.

IEC 60364-5-52 IEC 60228 NEC 210.19(A) NEC 215.2(A)
Circuit & Cable Data
Line-to-line for three phase, line-to-neutral for single phase.
Range 0 to 1. Leave at 0.85 if unknown.
One-way route length. The return path is handled by the multiplier k.
Enter your values and select Calculate.

Voltage Drop Formula

ΔU = k · I · ( R · cos φ + X · sin φ )
R = ρ75 · L / A // conductor resistance of the run
ρ75 = ρ20 · [ 1 + α · (75 − 20) ] // temperature correction
X = x′ · L // reactance from the formation table
ΔU % = 100 · ΔU / U
Uload = U − ΔU
Ploss = n · I² · R
Amin = k · I · L · ρ75 · cos φ / ( ΔUmax − k · I · x′ · L · sin φ )
SymbolMeaningUnit
ΔUVoltage drop along the cable runV
kPhase multiplier — √3 three phase, 2 single phase
nLoss multiplier — 3 three phase, 2 single phase
ILoad currentA
RConductor resistance of the run at 75 °CΩ
XConductor reactance of the runΩ
x′Reactance per metre, from the formation tableΩ/m
ρ20Resistivity at 20 °C — 1.72e-8 Cu, 2.82e-8 AlΩ·m
αTemperature coefficient — 0.00393 Cu, 0.00403 Al1/K
LOne-way route lengthm
AConductor cross-sectional areamm²
cos φLoad power factor
ΔUmaxPermitted drop in volts — 5 % of UV
The reactive term X·sinφ is independent of conductor area. On long runs at low power factor it can dominate, which is why the minimum-CSA expression subtracts it from the voltage budget before solving for area rather than ignoring it.

Worked Example

150 A three-phase feeder, 415 V, 150 m of 70 mm² copper

A 150 m submain feeds a distribution board drawing 150 A at 0.85 power factor from a 415 V three-phase supply. The cable is 70 mm² copper, laid in trefoil at low voltage, so x′ = 0.08 mΩ/m.

Resistivity at 75 °C
ρ75 = 1.72e-8 × [1 + 0.00393 × 55] = 0.020918 Ω·mm²/m
Conductor resistance
R = 0.020918 × 150 / 70 = 0.044824 Ω
Conductor reactance
X = 0.08e-3 × 150 = 0.012 Ω
Quadrature component
sin φ = √(1 − 0.85²) = 0.5268
Voltage drop
ΔU = √3 × 150 × (0.044824 × 0.85 + 0.012 × 0.5268) = 11.5411 V
Percentage drop
ΔU % = 100 × 11.5411 / 415 = 2.781 %
Voltage at load
Uload = 415 − 11.5411 = 403.46 V
Power loss
P = 3 × 150² × 0.044824 = 3025.61 W
Current density
150 / 70 = 2.1429 A/mm²
Minimum CSA for 5 %
36.26 mm², so 70 mm² has substantial margin
ΔU = 11.5411 V (2.781 %) · U at load 403.46 V · loss 3025.61 W · Amin 36.26 mm²
These are the default inputs above. Press Calculate and the same figures come back from the API.

Units & Accepted Ranges

InputUnitAccepted rangeDefault
Phase systemSingle or three phaseThree phase
Supply voltage UV> 0415
Load current IA> 0150
Power factor cos φ> 0 and ≤ 10.85
Route length Lm (ft)> 0150
Conductor CSAmm² (kcmil)> 070
MaterialCopper or aluminiumCopper
Formation0.08 to 0.30 mΩ/mLV trefoil
Conductor temperature is fixed at 75 °C and the pass/fail comparison is fixed at 5 %. Imperial entry converts at 1 ft = 0.3048 m and 1 kcmil = 0.5067 mm² before the calculation runs.

Cable Reactance by Formation

FormationVoltage classx′ (mΩ/m)Confidence
Trefoil / touchingLV ≤ 1 kV0.08±15 % vs datasheet
Flat formationLV ≤ 1 kV0.10±15 % vs datasheet
Touching trefoilMV 1–36 kV0.10Use manufacturer data
Spacing 1 × diameterMV 1–36 kV0.13Use manufacturer data
Spacing 2 × diameterMV 1–36 kV0.17±30–50 % possible
Spacing 3 × diameterMV 1–36 kV0.20Broad estimate only
XLPEHV > 33 kV0.30IEC 60287 software required
Reactance depends on conductor spacing and diameter, so these are typical values for preliminary work. For MV and HV design, take x′ from the cable manufacturer's datasheet.

Conductor Properties & Recommended Limits

Materialρ20 (Ω·m)α (1/K)ρ75 (Ω·mm²/m)Relative drop
Copper1.72e-80.003930.0209181.00
Aluminium2.82e-80.004030.0344511.65
Circuit typeRecommended limitReference
Lighting circuits3 %IEC 60364-5-52 Annex G
Other uses (power, motors)5 %IEC 60364-5-52 Annex G
Branch circuit3 %NEC 210.19(A) note
Feeder plus branch5 %NEC 215.2(A) note
Motor starting transient10–15 %Typical specification practice
An aluminium conductor of the same area drops about 65 % more voltage than copper. Aluminium is usually taken one or two standard sizes larger to compensate.

Frequently Asked Questions

What is the maximum allowable voltage drop in a cable?

IEC 60364-5-52 Annex G recommends 3 % for lighting circuits and 5 % for other uses, measured from the origin of the installation to the load. The NEC gives a comparable 3 % branch-circuit and 5 % combined feeder-plus-branch recommendation in informational notes to 210.19(A) and 215.2(A). Both are recommendations rather than hard limits, but most specifications adopt 5 % as the contractual ceiling. This calculator compares the computed percentage against 5 %.

Why does this calculator use 75 degrees C conductor temperature?

Conductor resistivity rises with temperature, so voltage drop computed at 20 °C is optimistic. IEC and NEC practice is to evaluate voltage drop at the conductor operating temperature. This calculator fixes the conductor at 75 °C, which raises copper resistivity from 1.72e-8 to about 2.09e-8 Ω·m — roughly 21 % more resistance and therefore roughly 21 % more resistive voltage drop than a 20 °C calculation would predict.

Does cable reactance matter for voltage drop?

Yes, and it is the term most often omitted. Reactive drop is proportional to sin φ, so at a power factor of 0.85 it carries about 53 % of the current in quadrature. For small conductors the resistive term dominates, but above roughly 70 to 95 mm² the reactance term becomes significant, and at low power factor or long runs it can decide whether a cable passes. This calculator includes the X sin φ term and reports the reactance used.

How do I calculate voltage drop for a single-phase circuit?

Use a multiplier of 2 instead of √3, because current flows out along the line conductor and back along the neutral, so the cable length is traversed twice. The formula becomes ΔU = 2 · I · (R cos φ + X sin φ). Select Single Phase in the calculator and it applies the factor of 2 automatically, and compares the drop against the single-phase supply voltage you enter.

What cable size do I need to keep voltage drop under 5%?

Rearranging the voltage drop formula for area gives A = k · I · L · ρ · cos φ / (ΔUmax − k · I · X · L · sin φ). The calculator reports this as the minimum CSA. Note that this is the minimum needed for voltage drop only — the conductor must also satisfy current-carrying capacity after derating and the adiabatic short-circuit withstand check, and either of those can demand a larger cable.

Related Electrical Calculators

← All Electrical Engineering Calculators

Results are for estimation and preliminary design. Verify against project specifications, cable manufacturer data and a qualified engineer before construction.

multicalci.com — free engineering calculators