MULTICALCI
Home / Electrical Calculators / Short Circuit Current Calculator
Electrical Engineering

Short Circuit Current Calculator

Calculate the prospective fault current at a low voltage board to IEC 60909, working through the grid source, the transformer and the connecting cable. Returns three-phase, phase-to-phase and phase-to-earth currents, the peak asymmetrical current, induction motor back-feed and the breaking capacity your switchgear needs.

IEC 60909 IEC 60947-2 c = 1.05
💥 Source, Transformer & Cable
Short circuit capacity at the HV side, from the utility.
Must not exceed %Z.
Enter 0 for a fault at the transformer LV terminals.
Total running induction motor rating on the bus. Enter 0 if none.
Enter the system data and select Calculate.

IEC 60909 Fault Current Formulae

Zbase = V² / Sbase  ·  Zgrid = V² / SkQ // referred to the LV side
Zxfmr = (%Z / 100) · Zbase  ·  Rxfmr = (%R / 100) · Zbase
X = √(Z² − R²) // split each element into R and X
Ztotal = √( (ΣR)² + (ΣX)² )
Ik3 = c · V / ( √3 · Ztotal ) // c = 1.05 for max LV fault
Ik2 = (√3 / 2) · Ik3  ·  Ik1 ≈ 0.85 · Ik3 // approximate, needs Z₀
κ = 1.02 + 0.98 · e−3R/X  ·  ip = κ · √2 · Ik3
Imot = 6 · Smot / ( √3 · V ) // back-feed, first few cycles
Sk = √3 · V · Ik3 // fault level in MVA
SymbolMeaningUnit
Ik3Symmetrical three-phase fault currentA
Ik2Phase-to-phase fault currentA
Ik1Phase-to-earth fault current, approximateA
ipPeak asymmetrical current, first half cycleA
κPeak factor from the X/R ratio
cVoltage factor, 1.05 for maximum LV fault
SkQGrid short circuit capacityMVA
%Z, %RTransformer impedance and resistance%
ImotInduction motor back-feed contributionA
SkFault levelMVA
The grid X/R ratio is fixed at 10 per IEC 60909 Table 3, cable reactance at 0.08 mΩ/m, and conductor resistance is taken at 20 °C, which is the correct choice for a maximum fault current calculation. Minimum fault current for protection grading uses c = 0.95 and conductor resistance at the maximum operating temperature, and is not covered here.

Worked Example

1000 kVA transformer, 500 MVA grid, 415 V board, 1500 kVA of motors

A 1000 kVA distribution transformer at 5 %Z and 1 %R feeds a 415 V main board through 10 m of 240 mm² copper. The utility declares 500 MVA at the HV terminals. The board carries 1500 kVA of running induction motors.

Base impedance
Zbase = 415² / 1 000 000 = 0.172225 Ω
Grid impedance at LV
Zgrid = 415² / 500 000 000 = 0.000344 Ω
Transformer impedance
Zxfmr = 0.05 × 0.172225 = 0.008611 Ω
Cable impedance
R = 0.000717 Ω, X = 0.0008 Ω over 10 m
Total impedance
Ztotal = 0.009894 Ω, X/R = 3.87
Three-phase fault
Ik3 = 1.05 × 415 / (√3 × 0.009894) = 25427.3 A = 25.43 kA
Phase-phase and phase-earth
Ik2 = 22020.7 A · Ik1 ≈ 21613.2 A
Peak factor and peak current
κ = 1.02 + 0.98 e−3/3.87 = 1.4717 → ip = 52922.6 A = 52.92 kA
Motor contribution
Imot = 6 × 1 500 000 / (√3 × 415) = 12520.8 A
Total including motors
25427.3 + 12520.8 = 37948.2 A = 37.95 kA
Fault level
Sk = √3 × 415 × 25427.3 / 10⁶ = 18.2772 MVA
Peak duty including motors
κ × √2 × 37948.2 = 78 980 A = 78.98 kA → 80 kA device
Ik3 = 25.43 kA · ip = 52.92 kA · with motors 37.95 kA · peak duty 78.98 kA · select 80 kA
Read the last two lines together. Sizing on the 52.92 kA peak alone would pick a 63 kA device, but the motor back-feed pushes the actual peak duty to 78.98 kA. This is the single most common way a fault study under-rates switchgear, and it is why the motor kVA field matters even though the contribution decays within a few cycles.

Units & Accepted Ranges

InputUnitAccepted rangeDefault
Grid fault levelMVA> 0500
LV bus voltageV> 0415
Transformer ratingkVA> 01000
Impedance %Z%> 0, typically 4–85
Resistance %R%> 0 and ≤ %Z1
Cable lengthm≥ 010
Cable CSAmm²> 0240
Motor loadkVA≥ 01500

Standard Breaking Capacities (IEC 60947-2)

Rating (kA)Typical applicationRating (kA)Typical application
6Domestic final circuits50Large LV main board
10Small commercial board631000–1600 kVA transformer
16Sub-distribution board80With significant motor load
25500 kVA transformer bus100Large industrial main board
31.5Common MV switchgear rating125Parallel transformers
40800 kVA transformer bus150 / 200Generation and heavy industry

Typical Transformer Impedance

RatingTypical %ZTypical %RX/RIsc at LV terminals
100 kVA4.0 %2.0 %1.73.5 kA
250 kVA4.0 %1.6 %2.38.8 kA
500 kVA4.5 %1.3 %3.315.6 kA
1000 kVA5.0 %1.0 %4.928.1 kA
1600 kVA6.0 %0.9 %6.637.5 kA
2000 kVA6.0 %0.8 %7.446.9 kA
2500 kVA6.25 %0.7 %8.956.2 kA
Indicative values at 415 V with an infinite source, for a sanity check when the nameplate is not to hand. A higher %Z lowers the fault current but worsens voltage regulation and motor starting, which is the trade-off behind the rating series.

Frequently Asked Questions

How do I calculate short circuit current?

Add the impedances of every element between the source and the fault, then divide the driving voltage by the total. IEC 60909 uses a voltage factor c of 1.05 for maximum fault current on low voltage systems, so the three-phase symmetrical current is c times the nominal voltage divided by √3 times the total impedance. The chain is normally the grid source impedance referred to the low voltage side, the transformer impedance from its %Z and %R, and the cable impedance to the point of fault.

What is the difference between Isc3, Isc2 and Isc1?

Ik3 is the symmetrical three-phase fault, normally the largest and the figure that sets switchgear breaking capacity. Ik2 is the phase-to-phase fault, which for a fault far from the generator is √3/2, about 86.6 % of Ik3. Ik1 is the phase-to-earth fault, and its true value depends on the zero-sequence impedance of the transformer and the earthing arrangement, so it can be either larger or smaller than Ik3. This calculator approximates Ik1 as 85 % of Ik3 and flags that an accurate figure needs zero-sequence data.

Why does peak current exceed the symmetrical value?

Current in an inductive circuit cannot change instantaneously, so a fault starting at a voltage zero produces a decaying DC offset on top of the symmetrical AC component. The first peak can therefore approach 2√2 times the symmetrical current. IEC 60909 quantifies this with the κ factor, which equals 1.02 + 0.98 e−3R/X. A stiff, highly inductive supply with a high X/R gives a κ near 1.8, while a cable-limited fault with a low X/R gives a κ near 1.1.

Do motors contribute to short circuit current?

Yes. During a fault a running induction motor is driven by the inertia of its load and briefly acts as a generator, feeding current back into the fault at roughly six times its full load current for the first few cycles. IEC 60909 requires this contribution to be included where the connected motor rating is significant relative to the transformer. It matters most for the making and peak duty of the switchgear, since the motor contribution decays within a few cycles and has largely disappeared by the time a breaker interrupts.

What breaking capacity does my breaker need?

The breaking capacity must exceed the prospective symmetrical fault current at the point of installation, and the making capacity must exceed the peak asymmetrical current including any motor contribution. Devices are rated in the standard series of 6, 10, 16, 20, 25, 31.5, 40, 50, 63, 80, 100, 125, 150 and 200 kA. Selecting on the symmetrical current alone under-rates the device wherever significant motor load is connected, because the peak duty is what the contacts actually face on closing.

Related Electrical Calculators

← All Electrical Engineering Calculators

Results are for estimation and preliminary design. A fault study for construction must use manufacturer transformer data, actual cable routes, zero-sequence impedance for earth faults and a minimum-fault case for protection grading. Verify with a qualified engineer.

multicalci.com — free engineering calculators