MULTICALCI
Home / Electrical Calculators / HV Cable Test Voltage Calculator
Electrical Engineering

HV Cable Test Voltage Calculator

Find the withstand test voltage, duration, governing standard and acceptance criterion for high voltage cable testing — VLF, AC site, AC factory or DC — together with the minimum insulation resistance for the cable length, corrected to the temperature you are testing at.

IEC 60502-2 / -4 IEC 60840 IEEE 400.2 IEEE 43
🔬 Cable & Test Details
Phase to earth, the first figure in a 6/10 kV designation.
Enter the cable details and select Calculate.
Safety. High voltage testing is potentially lethal. Only authorised and competent personnel may carry it out. Establish an exclusion zone, earth every conductor before connecting or disconnecting, and discharge the cable through a suitable resistor after every test — a tested cable holds a dangerous charge for a long time, particularly after a DC test.

Test Voltage Multipliers

Utest = k · U0 // k depends on method and occasion
IRmin = ( U0 + 1 ) · Lkm // MΩ, minimum acceptable
IRT = IRmin · 0.5(T − 20)/10 // halves every 10 °C
MethodNewMaintenanceAfter repairFactory
VLF 0.1 Hz2.0 U₀1.5 U₀1.73 U₀1.73 U₀
AC site withstand2.0 U₀1.5 U₀1.73 U₀2.5 U₀
AC factory (XLPE)2.5 U₀2.5 U₀2.5 U₀2.5 U₀
AC factory (EPR / PILC / PVC)2.0 U₀2.0 U₀2.0 U₀2.0 U₀
DC site (XLPE / EPR / PVC)3.0 U₀2.5 U₀3.0 U₀3.0 U₀
DC site (PILC)3.5 U₀2.5 U₀3.5 U₀3.5 U₀
Insulation resistanceNo withstand voltage — a 1 to 10 minute megger test at 500 to 5000 V DC
The AC factory row does not vary with the test occasion, because a routine factory test is defined by the standard rather than by why the cable is being tested. Selecting a different occasion alongside that method will not change the voltage.

Worked Example

6/10 kV XLPE cable, 500 m, VLF test after installation at 30 °C

A newly installed 6/10 kV XLPE cable, 500 m long with a PE outer sheath, is to be commissioned by VLF testing. Ambient at the time of test is 30 °C.

Test voltage
Utest = 2.0 × 6 = 12 kV at 0.1 Hz
Duration
60 min for a new installation
Governing standard
IEEE 400.2 / HD 620 (VLF 0.1 Hz)
Acceptance
No breakdown; tan δ below 4×10⁻³ indicates good insulation
Minimum insulation resistance at 20 °C
IR = (6 + 1) × 0.5 km = 3.50 MΩ
Corrected to 30 °C
IR = 3.50 × 0.5(30−20)/10 = 3.50 × 0.5 = 1.75 MΩ
Sheath test
DC 25 kV for 1 min, outer sheath to earth, no breakdown
12 kV VLF for 60 min · IR ≥ 3.50 MΩ at 20 °C, ≥ 1.75 MΩ measured at 30 °C · sheath DC 25 kV / 1 min
Note the direction of the temperature correction. The 3.50 MΩ limit applies at 20 °C, so a reading taken at 30 °C only has to reach 1.75 MΩ to be equivalent. Applying the correction the wrong way round is the usual reason a warm cable is wrongly condemned.

Test Method Comparison

MethodSuitsAdvantageLimitation
VLF 0.1 HzXLPE, EPRPortable set, service-like stress, allows tan δNot traditional for PILC
AC site withstandAll typesClosest to service conditionsResonant set is large and costly
AC factory routineAll typesFull type and routine regimeWorks only before installation
DC sitePILC onlySimple, compact equipmentSpace charge damages extruded insulation
Insulation resistanceAll typesFast, non-destructive, trendableFinds no weakness that only shows at stress

Insulation Resistance Temperature Correction

Test temperatureCorrection factorLimit for a 3.50 MΩ reference
0 °C4.0014.00 MΩ
10 °C2.007.00 MΩ
20 °C (reference)1.003.50 MΩ
30 °C0.501.75 MΩ
40 °C0.250.88 MΩ
50 °C0.1250.44 MΩ
Polarisation index is the ratio of the 10-minute to the 1-minute insulation resistance reading. Above 2 is good and below 1 is suspect. Because it is a ratio of two readings taken at the same temperature, it needs no correction, which is why it is more trustworthy than a single absolute value.

Cable Voltage Designations

Designation U₀/UU₀ to earthU between phasesVLF new test at 2 U₀
0.6/1 kV0.6 kV1 kV1.2 kV
1.8/3 kV1.8 kV3 kV3.6 kV
3.6/6 kV3.6 kV6 kV7.2 kV
6/10 kV6 kV10 kV12 kV
8.7/15 kV8.7 kV15 kV17.4 kV
12.7/22 kV12.7 kV22 kV25.4 kV
19/33 kV19 kV33 kV38 kV
38/66 kV38 kV66 kV76 kV
Only U₀ is needed for a test voltage, since U follows from it as √3 × U₀ in a three-phase system and the test stresses the insulation wall between conductor and screen. That is why this calculator asks for U₀ alone.

Frequently Asked Questions

What voltage should a HV cable be tested at?

Test voltage is a multiple of U₀, the phase-to-earth rating, and the multiple depends on the method and why you are testing. A new cable given a VLF or AC site test is normally taken to 2 U₀ for 60 minutes, a maintenance test to 1.5 U₀ for 30 minutes, and a test after a repair to 1.73 U₀. Factory routine testing goes higher, at 2.5 U₀ for XLPE. A 6 kV U₀ cable given a VLF test after installation is therefore tested at 12 kV.

Why is DC testing not recommended for XLPE cables?

A direct voltage injects and traps space charge in the polymer, which does not dissipate when the test ends. When the cable is re-energised on alternating voltage, that trapped charge adds to the peak of the AC waveform and produces local field enhancement far above the design stress. The result is a cable that passes its test and then fails weeks or months later. This is why IEEE 400 treats DC as a legacy method for extruded insulation and why VLF at 0.1 Hz has replaced it. DC remains acceptable for paper-insulated lead-covered cable.

What is VLF cable testing?

Very low frequency testing applies an alternating voltage at around 0.1 Hz instead of 50 or 60 Hz. Because the capacitive charging current of a cable is proportional to frequency, a 0.1 Hz source needs roughly one five-hundredth of the reactive power that a mains-frequency set would, so the equipment is small enough to carry to site. It stresses the insulation in a way that resembles service conditions without the space charge problem of DC, and it can be combined with tan δ and partial discharge measurement in the same connection.

How do I correct insulation resistance for temperature?

Insulation resistance roughly halves for every 10 °C rise, so readings must be corrected to a common reference, normally 20 °C, before they can be compared with earlier tests. The correction multiplies the reference value by 0.5 raised to the power of the temperature difference divided by ten. A 3.5 MΩ limit at 20 °C becomes 1.75 MΩ at 30 °C and 14 MΩ at 0 °C. Comparing an uncorrected summer reading against an uncorrected winter one is the most common way a healthy cable appears to have deteriorated.

What is the difference between Uo and U in cable ratings?

Cable ratings are written as U₀/U, for example 6/10 kV. U₀ is the rated power frequency voltage between one conductor and earth or the metallic screen, and U is the voltage between two phase conductors. In a three-phase system U = √3 × U₀, so a 6/10 kV cable has 6 kV to earth and 10 kV between phases. Withstand test voltages are always specified as a multiple of U₀, because the insulation wall between conductor and screen is what the test stresses.

Related Electrical Calculators

← All Electrical Engineering Calculators

Results are for guidance and preliminary planning. The governing document is always the cable manufacturer's recommendation and the project specification, which take precedence over the generic multipliers shown here. High voltage testing must only be carried out by competent authorised personnel under a written safe system of work.

multicalci.com — free engineering calculators